|
 |
Voltage Drop/Wire Sizing |
 |
|
Voltage Drop is the decrease in the voltage along
your 12V electrical wire. The longer the cable, the
larger the drop.
All lamps in your lighting plan require 11-12V to
glow correctly. The factors that determine
acceptable lamp performance (minimum voltage drop)
are:
- Shortest possible cable lengths
- Transformer regulation
- Cable (or wire) gauge
- Lamp load
What happens if I do not account for
Voltage Drop?
Your lamps will decrease in brightness the further
they are from the transformer.
How do I minimize Voltage Drop and
maximize Light Output?
- 1.Keep
wire lengths as short as possible
- 2.Select
the correct wire gauge (the smaller the wire, the greater the voltage drop)
How do I calculate Voltage Drop for
each fixture?
You must know these three values and plug the
numbers into this basic formula:
|
|
- A.=
Length of the wire
- B.=
Total # of watts for all lamps on that wire run
- C.=
Cable constant (determined by wire size)
| |
 |
If the voltage drop for any
fixture is greater than 2V, you must change the layout, or the cable(s)
or the transformer so that that fixture is not dimmed. |
|
WIRE SIZE |
CABLE CONSTANT |
|
#10 |
11920 |
|
#12 |
7500 |
|
#14 |
3500 |
|
#16 |
2200 |
|
#18 |
1380 | |
How
do I keep wire lengths really short?
Use these design guidelines to minimize voltage
drop.
- Avoid a single long cable with all
your fixtures attached to it! (“Standard Run”)
- Create several runs going in 2 or more
directions, attached to the same transformer terminals. (“Multiple Runs”)
- Use heavier gauge cable for the
primary cable attached to the transformer. Add lower gauged cable off the end of
the heavier cable forming a “T”. (“T-Run”)
- Use a single cable that begins and
ends at the transformer terminal to reduce voltage drop and produce more uniform
light output. Polarity must be matched. (“Loop Run”)
- Center the transformer in the middle
of the run.
- Substitute slightly lower voltage
lamps to reduce overall wattage
- Use multiple 12V transformers with
separate runs but all fed from a single 120V source.
- Add small transformers to the end of
the run.
How do I select the right wire
gauge?
To prevent voltage drop, you must select the right
cable for a 12V system. Distance of the run and
wattage load on the run will determine the cable
gauge/size. (NOTE:
Total Cable Length refers to each single run from a
transformer. Multiple runs are commonly used from a
single transformer.)
A quick guide is:
- Don’t use 16-gauge cable for more than
150 watts or 100 feet
- Don’t use 14-gauge cable for more than
200 watts or 150 feet
- Don’t use 12-gauge cable for more than
250 watts or 200 feet
50%
is the minimum light output for the last fixture on
any run. If you know the value of light output at
the end of your wire length, the % Light Output
Chart below identifies the required wire size,
length of straight run and wattage load.
Low Voltage Cable
Selection Guide |
| Total
cable length (ft) |
Max Watts on
ONE Cable Run |
#16 wire |
#14 wire |
#12 wire |
#10 wire |
| 300 |
NA |
NA |
0-60 |
0-90 |
| 200 |
NA |
0-60 |
90 |
130 |
| 100 |
75 |
120 |
175 |
275 |
| 80 |
95 |
140 |
250* |
350 |
| 50 |
150 |
215* |
250* |
360* |
| 40 |
155* |
215* |
250* |
360* |
| 30 |
155* |
215* |
250* |
360* |
| 20 |
155* |
215* |
250* |
360* |
| 10 |
155* |
215* |
250* |
360* |
| *maximum wire capacity | |
| % LIGHT OUTPUT |
Cable
Size |
Distance
from Transf (ft) |
Load
(Watts) |
|
50 |
100 |
150 |
200 |
250 |
300 |
|
12 |
10 |
99 |
98 |
97 |
95 |
94 |
89 |
|
20 |
98 |
95 |
89 |
83 |
80 |
79 |
|
30 |
97 |
89 |
82 |
82 |
72 |
70 |
|
40 |
95 |
83 |
79 |
71 |
63 |
56 |
|
50 |
90 |
80 |
73 |
63 |
54 |
52 |
|
80 |
83 |
71 |
56 |
45 |
35 |
26 |
|
100 |
80 |
63 |
52 |
35 |
25 |
20 |
|
200 |
63 |
35 |
20 |
10 |
7 |
5 |
|
300 |
52 |
20 |
8 |
5 |
NA |
NA |
|
10 |
10 |
99 |
99 |
98 |
97 |
96 |
92 |
|
20 |
99 |
97 |
92 |
91 |
88 |
84 |
|
30 |
98 |
92 |
89 |
84 |
81 |
80 |
|
40 |
98 |
91 |
84 |
80 |
78 |
73 |
|
50 |
97 |
88 |
81 |
78 |
72 |
65 |
|
80 |
90 |
80 |
73 |
63 |
55 |
51 |
|
100 |
88 |
78 |
65 |
55 |
45 |
40 |
|
200 |
79 |
55 |
40 |
36 |
18 |
11 |
|
300 |
65 |
40 |
21 |
11 |
8 |
6 | |
|
voltage drop chart
for #8-2 wire |
|
watts |
40 |
80 |
120 |
160 |
200 |
240 |
280 |
300 |
340 |
384 |
|
amps |
3.3 |
6.7 |
10 |
13.3 |
16.7 |
20 |
23.3 |
25 |
28.3 |
32 |
|
distance |
|
25 |
0.1 |
0.2 |
0.3 |
0.4 |
0.5 |
0.6 |
0.7 |
0.8 |
The NEC (National Electrical Code) limits all secondary wire runs to a maximum
of 20 amps |
|
50 |
0.2 |
0.4 |
0.6 |
0.9 |
1.1 |
1.3 |
1.5 |
1.6 |
|
75 |
0.3 |
0.6 |
1 |
1.3 |
1.6 |
1.9 |
2.2 |
2.4 |
|
100 |
0.4 |
0.9 |
1.3 |
1.7 |
2.1 |
2.6 |
3 |
3.2 |
|
125 |
0.5 |
1.1 |
1.6 |
2.1 |
2.7 |
3.2 |
3.7 |
4 |
|
150 |
0.6 |
1.3 |
1.9 |
2.6 |
3.2 |
3.8 |
4.5 |
4.8 |
|
175 |
0.7 |
1.5 |
2.2 |
3 |
3.7 |
4.5 |
5.2 |
5.6 |
|
200 |
0.8 |
1.7 |
2.6 |
3.4 |
4.3 |
5.1 |
6 |
6.4 |
|
225 |
0.9 |
1.9 |
2.9 |
3.8 |
4.8 |
5.8 |
6.7 |
7.2 |
|
|
|
250 |
1 |
2.1 |
3.2 |
4.3 |
5.3 |
6.4 |
7.5 |
8 |
|
|
|
275 |
1.1 |
2.3 |
3.5 |
4.7 |
5.9 |
7 |
8.2 |
8.8 |
|
|
|
300 |
1.2 |
2.6 |
3.8 |
5.1 |
6.4 |
7.7 |
9 |
9.6 |
|
|
|
325 |
1.3 |
2.8 |
4.2 |
5.5 |
6.9 |
8.3 |
9.7 |
|
|
|
|
350 |
1.4 |
3 |
4.5 |
6 |
7.5 |
9 |
|
|
|
|
|
375 |
1.5 |
3.2 |
4.8 |
6.4 |
8 |
9.6 |
|
|
|
|
|
400 |
1.6 |
3.4 |
5.1 |
6.8 |
8.5 |
10.2 |
|
|
|
|
|
425 |
1.7 |
3.6 |
5.4 |
7.3 |
9.1 |
|
|
|
|
|
|
450 |
1.8 |
3.8 |
5.8 |
7.7 |
9.6 |
|
|
|
|
|
|
475 |
1.9 |
4.1 |
6.1 |
8.1 |
10.1 |
|
|
|
|
|
|
500 |
2 |
4.3 |
6.4 |
8.5 |
|
|
|
|
|
|
|
525 |
2.1 |
4.5 |
6.7 |
9 |
|
|
|
|
|
|
|
550 |
2.2 |
4.7 |
7 |
9.4 |
|
|
|
|
|
|
|
575 |
2.3 |
4.9 |
7.4 |
9.8 |
|
|
|
|
|
|
|
600 |
2.5 |
5.1 |
7.7 |
10.2 |
|
|
|
|
|
|
|
625 |
2.6 |
5.3 |
8 |
|
|
|
|
|
|
|
|
650 |
2.7 |
5.5 |
8.3 |
|
|
|
|
|
|
|
|
675 |
2.8 |
5.8 |
8.6 |
|
|
|
|
|
|
|
|
700 |
2.9 |
6 |
9 |
|
|
|
|
|
|
|
|
725 |
3 |
6.2 |
9.3 |
|
|
|
|
|
|
|
|
750 |
3.2 |
6.4 |
9.6 |
|
|
|
|
|
|
|
|
775 |
3.3 |
6.6 |
9.9 |
|
|
|
|
|
|
|
|
800 |
3.4 |
6.8 |
10.2 |
|
|
|
|
|
|
|
|
825 |
3.5 |
7 |
|
|
|
|
|
|
|
|
|
850 |
3.6 |
7.3 |
|
|
|
|
|
|
|
|
|
875 |
3.7 |
7.5 |
|
|
|
|
|
|
|
|
|
900 |
3.8 |
7.7 |
|
|
|
|
|
|
|
|
|
925 |
3.9 |
7.9 |
|
|
|
|
|
|
|
|
|
950 |
4.1 |
8.1 |
|
|
|
|
|
|
|
|
|
975 |
4.2 |
8.3 |
|
|
|
|
|
|
|
|
|
1000 |
4.3 |
8.5 |
|
|
|
|
|
|
|
|
|
voltage drop chart
for #10-2 wire |
|
watts |
18 |
35 |
70 |
105 |
140 |
175 |
210 |
245 |
280 |
288 |
|
amps |
1.5 |
2.9 |
5.8 |
8.8 |
11.7 |
14.6 |
17.5 |
20.4 |
23.3 |
24 |
|
distance |
|
25 |
0.1
| 0.2 |
0.3 |
0.5 |
0.6 |
0.8 |
0.9 |
1.1 |
1.3 |
1.3 |
|
50 |
0.2 |
0.3 |
0.6 |
0.9 |
1.3 |
1.6 |
1.9 |
2.2 |
2.5 |
2.6 |
|
75 |
0.2 |
0.5 |
0.9 |
1.4 |
1.9 |
2.4 |
2.8 |
3.3 |
3.8 |
3.9 |
|
100 |
0.3 |
0.6 |
1.3 |
1.9 |
2.5 |
3.2 |
3.8 |
4.4 |
5 |
5.2 |
|
125 |
0.4 |
0.8 |
1.6 |
2.4 |
3.2 |
3.9 |
4.7 |
5.5 |
6.3 |
6.5 |
|
150 |
0.5 |
0.9 |
1.9 |
2.8 |
3.8 |
4.7 |
5.7 |
6.6 |
7.6 |
7.8 |
|
175 |
0.6 |
1.1 |
2.2 |
3.3 |
4.4 |
5.5 |
6.6 |
7.7 |
8.8 |
9.1 |
|
200 |
0.6 |
1.3 |
2.5 |
3.8 |
5 |
6.3 |
7.6 |
8.8 |
10.1 |
10.4 |
|
225 |
0.7 |
1.4 |
2.8 |
4.3 |
5.7 |
7.1 |
8.5 |
9.9 |
|
|
|
250 |
0.8 |
1.6 |
3.2 |
4.7 |
6.3 |
7.9 |
9.5 |
|
|
|
|
275 |
0.9 |
1.7 |
3.5 |
5.2 |
6.9 |
8.7 |
10.4 |
|
|
|
|
300 |
1 |
1.9 |
3.8 |
5.7 |
7.6 |
9.5 |
|
|
|
|
|
325 |
1.1 |
2 |
4.1 |
6.1 |
8.2 |
10.2 |
|
|
|
|
|
350 |
1.1 |
2.2 |
4.4 |
6.6 |
8.8 |
|
|
|
|
|
|
375 |
1.2 |
2.4 |
4.7 |
7.1 |
9.5 |
|
|
|
|
|
|
400 |
1.3 |
2.5 |
5 |
7.6 |
10.1 |
|
|
|
|
|
|
425 |
1.4 |
2.7 |
5.4 |
8 |
|
|
|
|
|
|
|
450 |
1.5 |
2.8 |
5.7 |
8.5 |
|
|
|
|
|
|
|
475 |
1.5 |
3 |
6 |
9 |
|
|
|
|
|
|
|
500 |
1.6 |
3.2 |
6.3 |
9.5 |
|
|
|
|
|
|
|
525 |
1.7 |
3.3 |
6.6 |
9.9 |
|
|
|
|
|
|
|
550 |
1.8 |
3.5 |
6.9 |
10.4 |
|
|
|
|
|
|
|
575 |
1.9 |
3.6 |
7.2 |
|
|
|
|
|
|
|
|
600 |
1.9 |
3.8 |
7.6 |
|
|
|
|
|
|
|
|
625 |
2 |
3.9 |
7.9 |
|
|
|
|
|
|
|
|
650 |
2.1 |
4.1 |
8.2 |
|
|
|
|
|
|
|
|
675 |
2.2 |
4.3 |
8.5 |
|
|
|
|
|
|
|
|
700 |
2.3 |
4.4 |
8.8 |
|
|
|
|
|
|
|
|
725 |
2.3 |
4.6 |
9.1 |
|
|
|
|
|
|
|
|
750 |
2.4 |
4.7 |
9.5 |
|
|
|
|
|
|
|
|
775 |
2.5 |
4.9 |
9.8 |
|
|
|
|
|
|
|
|
800 |
2.6 |
5 |
10.1 |
|
|
|
|
|
|
|
|
825 |
2.7 |
5.2 |
10.4 |
|
|
|
|
|
|
|
|
850 |
2.8 |
5.4 |
|
|
|
|
|
|
|
|
|
875 |
2.8 |
5.5 |
|
|
|
|
|
|
|
|
|
900 |
2.9 |
5.7 |
|
|
|
|
|
|
|
|
|
925 |
3 |
5.8 |
|
|
|
|
|
|
|
|
|
950 |
3.1 |
6 |
|
|
|
|
|
|
|
|
|
975 |
3.2 |
6.1 |
|
|
|
|
|
|
|
|
|
1000 |
3.2 |
6.3 |
|
|
|
|
|
|
|
|
|
voltage drop chart
for #12-2 wire |
|
watts |
20 |
40 |
60 |
80 |
100 |
120 |
140 |
160 |
180 |
192 |
|
amps |
1.7 |
3.3 |
5 |
6.7 |
8.3 |
10 |
11.7 |
13.3 |
15 |
16 |
|
distance |
|
25 |
0.1 |
0.3 |
0.4 |
0.5 |
0.7 |
0.8 |
1 |
1.1 |
1.2 |
1.3 |
|
50 |
0.3 |
0.5 |
0.8 |
1.1 |
1.4 |
1.6 |
1.9 |
2.2 |
2.4 |
2.6 |
|
75 |
0.4 |
0.8 |
1.2 |
1.6 |
2 |
2.4 |
2.8 |
3.2 |
3.7 |
3.9 |
|
100 |
0.5 |
1.1 |
1.6 |
2.2 |
2.7 |
3.2 |
3.8 |
4.3 |
4.9 |
5.2 |
|
125 |
0.7 |
1.4 |
2 |
2.7 |
3.4 |
4.1 |
4.7 |
5.4 |
6.1 |
6.5 |
|
150 |
0.8 |
1.6 |
2.4 |
3.2 |
4.1 |
4.9 |
5.7 |
6.5 |
7.3 |
7.8 |
|
175 |
1 |
1.9 |
2.8 |
3.8 |
4.7 |
5.7 |
6.6 |
7.6 |
8.5 |
9.1 |
|
200 |
1.1 |
2.2 |
3.2 |
4.3 |
5.4 |
6.5 |
7.6 |
8.6 |
9.7 |
|
|
225 |
1.2 |
2.4 |
3.7 |
4.9 |
6.1 |
7.3 |
8.5 |
9.7 |
|
|
|
250 |
1.4 |
2.7 |
4.1 |
5.4 |
6.8 |
8.1 |
9.5 |
|
|
|
|
275 |
1.5 |
3 |
4.5 |
5.9 |
7.4 |
8.9 |
10.4 |
|
|
|
|
300 |
1.6 |
3.2 |
4.9 |
6.5 |
8.1 |
|
|
|
|
|
|
325 |
1.8 |
3.5 |
5.3 |
7 |
8.8 |
|
|
|
|
|
|
350 |
1.9 |
3.8 |
5.7 |
7.6 |
9.5 |
|
|
|
|
|
|
375 |
2 |
4.1 |
6.1 |
8.1 |
10.1 |
|
|
|
|
|
|
400 |
2.2 |
4.3 |
6.5 |
8.6 |
|
|
|
|
|
|
|
425 |
2.3 |
4.6 |
6.9 |
9.2 |
|
|
|
|
|
|
|
450 |
2.4 |
4.9 |
7.3 |
9.7 |
|
|
|
|
|
|
|
475 |
2.6 |
5.1 |
7.7 |
10.3 |
|
|
|
|
|
|
|
500 |
2.7 |
5.4 |
8.1 |
10.8 |
|
|
|
|
|
|
|
525 |
2.8 |
5.7 |
8.5 |
|
|
|
|
|
|
|
|
550 |
3 |
5.9 |
8.9 |
|
|
|
|
|
|
|
|
575 |
3.1 |
6.2 |
9.3 |
|
|
|
|
|
|
|
|
600 |
3.2 |
6.5 |
9.7 |
|
|
|
|
|
|
|
|
625 |
3.4 |
6.8 |
10.1 |
|
|
|
|
|
|
|
|
650 |
3.5 |
7 |
|
|
|
|
|
|
|
|
|
675 |
3.7 |
7.3 |
|
|
|
|
|
|
|
|
|
700 |
3.8 |
7.6 |
|
|
|
|
|
|
|
|
|
725 |
3.9 |
7.8 |
|
|
|
|
|
|
|
|
|
750 |
4.1 |
8.1 |
|
|
|
|
|
|
|
|
|
775 |
4.2 |
8.4 |
|
|
|
|
|
|
|
|
|
800 |
4.3 |
8.6 |
|
|
|
|
|
|
|
|
|
825 |
4.5 |
8.9 |
|
|
|
|
|
|
|
|
|
850 |
4.6 |
9.2 |
|
|
|
|
|
|
|
|
|
875 |
4.7 |
9.5 |
|
|
|
|
|
|
|
|
|
900 |
4.9 |
9.7 |
|
|
|
|
|
|
|
|
|
925 |
5 |
10 |
|
|
|
|
|
|
|
|
|
950 |
5.1 |
10.3 |
|
|
|
|
|
|
|
|
|
975 |
5.3 |
|
|
|
|
|
|
|
|
|
|
1000 |
5.4 |
|
|
|
|
|
|
|
|
|
How do I select the right
transformer?
Low voltage lighting systems and fixtures use a
transformer to step the 120VAC line voltage down to
12VAC. To simplify installation, many transformers
have multiple taps on the low-voltage side of the
unit that provide 12V, 13V, and 14V output (up to
22V). Most transformers include built in
programmable on/off timers. Others may include a
photo sensor that activates the lights from dusk to
dawn.
To determine the proper size transformer:
- 1.
Add up the wattages of all the fixtures to be connected to that transformer ONLY
- 2.
Divide the total by .8
- 3.
Round up to the nearest available transformer size
Ex: Twelve fixtures with 18 watt lamps.
12 x 18 = 218. 216 / .8 = 270.
Closest transformer is 300 watts.
How do I select the right tap on the
transformer?
If the total wattage of all fixtures on the line =
100 watts AND the total distance of cable line is
200 feet AND you are using 12 gauge wire, THEN use a
17V tap to eliminate voltage drop. How did we get
that? See the charts below for more information.
|
transformer tap chart
for #8-2 wire |
|
watts |
40 |
80 |
120 |
160 |
200 |
240 |
280 |
300 |
340 |
384 |
|
amps |
3.3 |
6.7 |
10 |
13.3 |
16.7 |
20 |
23.3 |
25 |
28.3 |
32 |
|
distance |
|
25 |
12
| 12 |
12 |
12 |
13 |
13 |
13 |
13 |
The NEC (National Electrical Code) limits all secondary wire runs to a maximum
of 20 amps |
|
50 |
12 |
12 |
13 |
13 |
13 |
13 |
13 |
14 |
|
75 |
12 |
13 |
13 |
13 |
14 |
14 |
14 |
14 |
|
100 |
12 |
13 |
13 |
14 |
14 |
15 |
15 |
15 |
|
125 |
13 |
13 |
14 |
14 |
15 |
15 |
16 |
16 |
|
150 |
13 |
13 |
14 |
15 |
15 |
16 |
16 |
17 |
|
175 |
13 |
13 |
14 |
15 |
16 |
16 |
17 |
18 |
|
200 |
13 |
14 |
15 |
15 |
16 |
17 |
18 |
18 |
|
225 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
19 |
|
|
|
250 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
20 |
|
|
|
275 |
13 |
14 |
16 |
17 |
18 |
19 |
20 |
21 |
|
|
|
300 |
13 |
15 |
16 |
17 |
18 |
20 |
21 |
22 |
|
|
|
325 |
13 |
15 |
16 |
18 |
19 |
20 |
22 |
|
|
|
|
350 |
13 |
15 |
16 |
18 |
19 |
21 |
|
|
|
|
|
375 |
14 |
15 |
17 |
18 |
20 |
22 |
|
|
|
|
|
400 |
14 |
15 |
17 |
19 |
21 |
22 |
|
|
|
|
|
425 |
14 |
16 |
17 |
19 |
21 |
|
|
|
|
|
|
450 |
14 |
16 |
18 |
20 |
22 |
|
|
|
|
|
|
475 |
14 |
16 |
18 |
20 |
22 |
|
|
|
|
|
|
500 |
14 |
16 |
18 |
21 |
|
|
|
|
|
|
|
525 |
14 |
16 |
19 |
21 |
|
|
|
|
|
|
|
550 |
14 |
17 |
19 |
21 |
|
|
|
|
|
|
|
575 |
14 |
17 |
19 |
22 |
|
|
|
|
|
|
|
600 |
15 |
17 |
20 |
22 |
|
|
|
|
|
|
|
625 |
15 |
17 |
20 |
|
|
|
|
|
|
|
|
650 |
15 |
18 |
20 |
|
|
|
|
|
|
|
|
675 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
700 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
725 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
750 |
15 |
18 |
22 |
|
|
|
|
|
|
|
|
775 |
15 |
19 |
22 |
|
|
|
|
|
|
|
|
800 |
15 |
19 |
22 |
|
|
|
|
|
|
|
|
825 |
16 |
19 |
|
|
|
|
|
|
|
|
|
850 |
16 |
19 |
|
|
|
|
|
|
|
|
|
875 |
16 |
19 |
|
|
|
|
|
|
|
|
|
900 |
16 |
20 |
|
|
|
|
|
|
|
|
|
925 |
16 |
20 |
|
|
|
|
|
|
|
|
|
950 |
16 |
20 |
|
|
|
|
|
|
|
|
|
975 |
16 |
20 |
|
|
|
|
|
|
|
|
|
1000 |
16 |
21 |
|
|
|
|
|
|
|
|
|
transformer tap chart
for #10-2 wire |
|
watts |
18 |
35 |
70 |
105 |
140 |
175 |
210 |
245 |
280 |
288 |
|
amps |
1.5 |
2.9 |
5.8 |
8.8 |
11.7 |
14.6 |
17.5 |
20.4 |
23.3 |
24 |
|
distance |
|
25 |
12
| 12 |
12 |
13 |
13 |
13 |
13 |
13 |
13 |
13 |
|
50 |
12 |
12 |
13 |
13 |
13 |
14 |
14 |
14 |
15 |
15 |
|
75 |
12 |
13 |
13 |
13 |
14 |
14 |
15 |
15 |
16 |
16 |
|
100 |
12 |
13 |
13 |
14 |
15 |
15 |
16 |
16 |
17 |
17 |
|
125 |
12 |
13 |
14 |
14 |
15 |
16 |
17 |
18 |
18 |
19 |
|
150 |
13 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
20 |
21 |
|
175 |
13 |
13 |
14 |
15 |
16 |
18 |
19 |
20 |
21 |
21 |
|
200 |
13 |
13 |
15 |
16 |
17 |
18 |
20 |
21 |
22 |
22 |
|
225 |
13 |
13 |
15 |
16 |
18 |
19 |
21 |
22 |
|
|
|
250 |
13 |
14 |
15 |
17 |
18 |
20 |
22 |
|
|
|
|
275 |
13 |
14 |
16 |
17 |
19 |
21 |
22 |
|
|
|
|
300 |
13 |
14 |
16 |
18 |
20 |
22 |
|
|
|
|
|
325 |
13 |
14 |
16 |
18 |
20 |
22 |
|
|
|
|
|
350 |
13 |
14 |
16 |
19 |
21 |
|
|
|
|
|
|
375 |
13 |
14 |
17 |
19 |
22 |
|
|
|
|
|
|
400 |
13 |
15 |
17 |
20 |
22 |
|
|
|
|
|
|
425 |
13 |
15 |
17 |
20 |
|
|
|
|
|
|
|
450 |
14 |
15 |
18 |
21 |
|
|
|
|
|
|
|
475 |
14 |
15 |
18 |
21 |
|
|
|
|
|
|
|
500 |
14 |
15 |
18 |
22 |
|
|
|
|
|
|
|
525 |
14 |
15 |
19 |
22 |
|
|
|
|
|
|
|
550 |
14 |
16 |
19 |
22 |
|
|
|
|
|
|
|
575 |
14 |
16 |
19 |
|
|
|
|
|
|
|
|
600 |
14 |
16 |
20 |
|
|
|
|
|
|
|
|
625 |
14 |
16 |
20 |
|
|
|
|
|
|
|
|
650 |
14 |
16 |
20 |
|
|
|
|
|
|
|
|
675 |
14 |
16 |
21 |
|
|
|
|
|
|
|
|
700 |
14 |
16 |
21 |
|
|
|
|
|
|
|
|
725 |
14 |
17 |
21 |
|
|
|
|
|
|
|
|
750 |
14 |
17 |
22 |
|
|
|
|
|
|
|
|
775 |
15 |
17 |
22 |
|
|
|
|
|
|
|
|
800 |
15 |
17 |
22 |
|
|
|
|
|
|
|
|
825 |
15 |
17 |
22 |
|
|
|
|
|
|
|
|
850 |
15 |
17 |
|
|
|
|
|
|
|
|
|
875 |
15 |
18 |
|
|
|
|
|
|
|
|
|
900 |
15 |
18 |
|
|
|
|
|
|
|
|
|
925 |
15 |
18 |
|
|
|
|
|
|
|
|
|
950 |
15 |
18 |
|
|
|
|
|
|
|
|
|
975 |
15 |
18 |
|
|
|
|
|
|
|
|
|
1000 |
15 |
18 |
|
|
|
|
|
|
|
|
|
transformer tap chart
for #12-2 wire |
|
watts |
20 |
40 |
60 |
80 |
100 |
120 |
140 |
160 |
180 |
192 |
|
amps |
1.7 |
3.3 |
5 |
6.7 |
8.3 |
10 |
11.7 |
13.3 |
15 |
16 |
|
distance |
|
25 |
12
| 12 |
12 |
13 |
13 |
13 |
13 |
13 |
13 |
13 |
|
50 |
12 |
13 |
13 |
13 |
13 |
14 |
14 |
14 |
14 |
15 |
|
75 |
12 |
13 |
13 |
14 |
14 |
14 |
15 |
15 |
16 |
16 |
|
100 |
13 |
13 |
14 |
14 |
15 |
15 |
16 |
16 |
17 |
17 |
|
125 |
13 |
13 |
14 |
15 |
15 |
16 |
17 |
17 |
18 |
18 |
|
150 |
13 |
14 |
14 |
15 |
16 |
17 |
18 |
18 |
19 |
20 |
|
175 |
13 |
14 |
15 |
16 |
17 |
18 |
19 |
20 |
21 |
21 |
|
200 |
13 |
14 |
15 |
16 |
17 |
18 |
20 |
21 |
22 |
|
|
225 |
13 |
14 |
16 |
17 |
18 |
19 |
21 |
22 |
|
|
|
250 |
13 |
15 |
16 |
17 |
19 |
20 |
21 |
|
|
|
|
275 |
13 |
15 |
16 |
18 |
19 |
21 |
22 |
|
|
|
|
300 |
14 |
15 |
17 |
18 |
20 |
|
|
|
|
|
|
325 |
14 |
16 |
17 |
19 |
21 |
|
|
|
|
|
|
350 |
14 |
16 |
18 |
20 |
21 |
|
|
|
|
|
|
375 |
14 |
16 |
18 |
20 |
22 |
|
|
|
|
|
|
400 |
14 |
16 |
18 |
21 |
|
|
|
|
|
|
|
425 |
14 |
17 |
19 |
21 |
|
|
|
|
|
|
|
450 |
14 |
17 |
19 |
22 |
|
|
|
|
|
|
|
475 |
15 |
17 |
20 |
22 |
|
|
|
|
|
|
|
500 |
15 |
17 |
20 |
23 |
|
|
|
|
|
|
|
525 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
550 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
575 |
15 |
18 |
21 |
|
|
|
|
|
|
|
|
600 |
15 |
18 |
22 |
|
|
|
|
|
|
|
|
625 |
15 |
19 |
22 |
|
|
|
|
|
|
|
|
650 |
16 |
19 |
|
|
|
|
|
|
|
|
|
675 |
16 |
19 |
|
|
|
|
|
|
|
|
|
700 |
16 |
20 |
|
|
|
|
|
|
|
|
|
725 |
16 |
20 |
|
|
|
|
|
|
|
|
|
750 |
16 |
20 |
|
|
|
|
|
|
|
|
|
775 |
16 |
20 |
|
|
|
|
|
|
|
|
|
800 |
16 |
21 |
|
|
|
|
|
|
|
|
|
825 |
16 |
21 |
|
|
|
|
|
|
|
|
|
850 |
17 |
21 |
|
|
|
|
|
|
|
|
|
875 |
17 |
21 |
|
|
|
|
|
|
|
|
|
900 |
17 |
22 |
|
|
|
|
|
|
|
|
|
925 |
17 |
22 |
|
|
|
|
|
|
|
|
|
950 |
17 |
22 |
|
|
|
|
|
|
|
|
|
975 |
17 |
|
|
|
|
|
|
|
|
|
|
1000 |
17 |
|
|
|
|
|
|
|
|
|
Real Life Voltage Drop Example
You want to install 10w lights about 10 feet apart
down a 250' sidewalk leading to a driveway. The
initial plan calls for the transformer to be
installed at one end of the run.
What size transformer do you need?
With a cable run of 250 feet and fixtures spaced 10
feet apart you will need 25 fixtures. If each lamp
is 10w the total load will 250w. At minimum you will
need a 2 X 300w (600w total) transformer with 12, 13
and 14V taps.
What gauge wire do you need?
Move the transformer to the mid-point of the run so
that the cable runs would be only 125' each. Each
125' of 10/2 gauge low voltage cable would be fed
from one of the two 300w outputs and should be
center-fed i.e. like a "T" with the one arm folded;
this reduces the overall length of each leg (spliced
at the center point) to 62 1/2'. This results in a
120 to 130w load on each 300w output, which should
eliminate any problems with voltage drop (using the
13V or 14V tap should give you about 10 - 11.5V for
each fixture.
What are the voltage drop considerations?
If the transformer stays at the end of the 250’ run,
use the
ABC
voltage drop formula to estimate how many volts will
be lost at the last fixture. In this case, multiply
the Cable Constant x 2 for long runs.
Voltage
Drop = |
A
x B |
| C
x 2 | |
- A.=
Length of the wire
- B.=
Total # of watts for all lamps on that wire run
- C.=
Cable constant (determined by wire size)
|
 |
|
WIRE SIZE |
CABLE CONSTANT |
|
#10 |
11920 |
|
#12 |
7500 |
|
#14 |
3500 |
|
#16 |
2200 |
|
#18 |
1380 |
So running 250 feet of #10 cable with 250 watts
would result in an unacceptable 5-10v drop at the
end of the run.
What are possible solutions?
Be creative and break up the run!
Remember to always use a voltmeter or multimeter to
measure actual voltage drop and plug into the
necessary tap on the transformer to provide 10.5-12
volts to all fixtures.
- Run 1: Run
#10 low voltage cable for the first 10 fixtures and plug it into the 12v tap on
the transformer. Using the ABC formula, you would get a .83 volt drop [(100 x
100)/11960}.
- Run 2 Option 1: Add
the remaining 15 fixtures at a 250' a serial run. Using the ABC formula, you
would get an unacceptable voltage drop of 3-6V.
- Run 2 Option 2: Loop
the wire at the end of the run back to the transformer to ease the voltage drop.
Total cable would be 600’ #10.
- Run 2 Option 3: Use
the "T" run for these 15 fixtures with low voltage cable by running #8 wire 175'
to the center and then branch off 75' each way with #10 cable. Total cable would
be 250' of #10 cable and 175' of #8 cable.
|
|
|
 |
|
|
|